DRG-AR Series from $250
DIN Rail Alarm Modules for Thermocouples, RTD, AC and DC Voltage and Current

DRG-AR Alarm Modules

The DRG-AR Series modules are a family of DIN rail mount limit alarms with dual setpoints and two contact closure (relay) outputs. The field configurable input and alarm functions offer flexible setpoint capability. Modules are available for a variety of input types including thermocouples, RTDs, DC and AC current and voltages.

Each module can be set to a number of input ranges via an input selector switch. The alarm points and dead band are adjusted by potentiometers.

Diagnostic LEDs
All modules are equipped with 3 front panel LEDs. The first is a dual function LED labeled input. This green LED indicates line power and input signal status. Two red LEDs indicate the relay state for each setpoint. An illuminated red LED indicates the tripped condition.

Output
The DRG-AR Series modules are equipped with two SPDT relays, rated at 120 Vac or 28 Vdc at 5 amperes. Each of these relays is independently controlled by the field configurable setpoint and deadband.

Operation
The field configurable limit alarm setpoints can be configured for HI or LO, failsafe or non-failsafe operation. Each of the setpoints has a respective HI or LO deadband. In a tripped condition, the setpoint is exceeded and the appropriate red LED will illuminate. The trip will reset only when the process falls below the HI deadband or rises above the low deadband. In failsafe operation, the relay is energized when the process is below the HI setpoint or above the LO setpoint (opposite for non-fail-safe). In the fail-safe mode, a power failure results in an alarm state output.

Dynamic DeadBand
LSI circuitry in the DRG-AR Series prevents false trips by repeatedly sampling the input. The input must remain beyond the setpoint for 100 milliseconds to qualify as a valid trip condition. Likewise, the input must fall outside the deadband and remain there for 100 milliseconds to return the alarm to an untripped condition. This, effectively, results in a dynamic deadband.


VIEW an Adobe Acrobat pdf file for more product info (requires Acrobat Reader).

VIEW the complete operator's manual for the DRG-AR-TC thermocouple alarm module (requires Acrobat Reader).

VIEW the complete operator's manual for the DRG-AR-RTD RTD alarm module (requires Acrobat Reader).

VIEW the complete operator's manual for the DRG-AR-DC DC voltage and current alarm module (requires Acrobat Reader).

VIEW the complete operator's manual for the DRG-AR-AC AC voltage and current alarm module (requires Acrobat Reader).